Newmar

Integrated Power System w/ 5 AH battery, Output adjustment range 40-60 VDC, Positive Ground

Part Number: IPS-48-11

List Price: $3,052.00

(Request quote for discounted pricing)

Special Order

Quantity

- +

The Integrated Power System (IPS) is a unique multifunction power supply which incorporates built-in battery back-up and numerous power accessories within a single 2RU (3.5”) chassis, thus eliminating time-consuming system integration, component sourcing and installation, while saving precious rack space–ideal for any low-to-medium power application requiring AC fault tolerant operation.

A precision regulated power supply/charger, back-up battery, low voltage battery disconnect, output metering, LED status and Form C alarm contacts are all pre-wired and calibrated within the unit for plug-and-play operation. Plug-in terminals are provided for easy wiring of an additional parallel rectifier input, or external batteries for increased back-up capacity.

The batteries are always in-line with the load, thus there is no interruption from relays or transfer switches in the event of AC loss. Batteries are recharged when AC is restored. A manual battery disconnect switch allows internal or external battery service or replacement while the system is running. Models available for -48, +24 and +12 volt applications.

Features

* Precision regulated power supply simultaneously maintains batteries at peak charge and supplies system load

* Built-in, sealed, maintenance free, lead acid batteries instantly power load during AC failure – no switch-over delay. 3-5 year average life. Terminals provided for additional external batteries for increased back-up capacity

* Terminals provided for easy addition of parallel rectifier. (48V and 24V models only)

* Low voltage battery disconnect, automatic or manual setting

* Numerous front panel monitors – L.E.D. status indicators and digital ammeter/voltmeter

* Form C summary failure alarm contacts; loss of internal rectifier output, loss of external rectifier output, LVBD contactor open. AC input failure alarm contacts optional

* Numerous protection features – AC input breaker, internal battery breaker, auto thermal shutdown/ recovery, current-limiting, short-circuit and overvoltage protection

* 19” rack, 6” forward rackmount brackets provided